Compliance to european union directives, Installation in zone 1, Compliance to european union directives -2 – Rockwell Automation 1797-IRT8 FLEX Ex Thermocouple/RTD/mV Input Module User Manual User Manual
Page 26: Emc directive -2 ex directive -2, Installation in zone 1 -2

Publication 1797-6.5.2 - February 2001
3-2 How to Install Your FLEX Ex Thermocouple/RTD/mV Module
Compliance to European
Union Directives
If this product has the CE mark, it is approved for installation within
the European and EEA regions. It has been designed and tested to
meet the following directives.
EMC Directive
This product is tested to meet the Council Directive 89/336/EC
Electromagnetic Compatibility (EMC) by applying the following
standards, in whole or in part, documented in a technical construction
file:
•
EN 50081-2 EMC - Generic Emission Standard, Part 2 - Industrial
Environment
•
EN 50082-2 EMC - Generic Immunity Standard, Part 2 - Industrial
Environment
This product is intended for use in an industrial environment.
Ex Directive
This product is tested to meet the Council Directive 94/9/EC (ATEX
100a) Equipment and Protective Systems Intended for Use in
Potentially Explosive Atmospheres by applying the following
standards:
•
EN50014:1992, Electrical Apparatus for Potentially Explosive
Atmospheres
•
EN50020:1994, Electrical Apparatus for Potentially Explosive
Atmospheres - Intrinsic Safety “i”
•
prEN50284:1997, Special requirements for construction, test and
marking of electrical apparatus of equipment group II, category
1G
Installation in Zone 1
This module must not be exposed to the environment. Provide a
suitable metal enclosure.
ATTENTION
!
This module cannot be used in an
intrinsically safe environment after it has
been exposed to non-intrinsically safe
signals.