Troubleshooting

Troubleshooting

Description

Possible Cause

Corrective Action

CHANGE BATTERY!

The battery voltage is <3.6V. This message is
displayed after switching on the memory
module programmer.

Change the batteries; see

page 4

.

FILE VER INCOMP!

Attempted to edit a memory module.

Function not available.

READ ONLY FILE!

You have tried to edit or delete a file.

Function not available.

EPM DAMAGED!

The memory module in the EPM port is
defective.

Contact Rockwell Automation technical support
or exchange the defective memory module.

The memory module is not placed correctly in
the EPM port.

Plug the memory module correctly in the port.

EPM MISSING!

There is no memory module in the EPM port to
which you are attempting to transfer data or
edit.

Press Menu now to return to the main menu.
Plug a memory module in the EPM port.

EPM TOO SMALL!

The memory module in the EPM port does not
have sufficient memory for the file you are
attempting to copy.

Contact Rockwell Automation technical
support.

INTERNAL ERROR!

Internal device error.

Contact your Rockwell Automation
representative.

INVALID INT CFG

Attempting to reconfigure the memory module
programmer.

Function not available.

WRONG PASSWORD

Password protection is activated and you have
entered the wrong password after switch-on.

The password function has no affect on the
ability to duplicate Bulletin 2097 memory
modules. No action is required.

MASTER DAMAGED!

The memory module in the master port is
defective.

Press Menu to return to the main menu. Plug a
memory module in the master port.

The memory module is not placed correctly in
the master port.

The message does not indicate an error but only
serves as a note.
The message is displayed only for a short time.

MASTER MISSING

Seen on powerup if there is no memory module
in the master port.

Information only.

Programmer is trying to read data from the
master port but cannot detect a memory
module in this port.

Insert a valid memory module into the master
port.

INVALID MASTER!

The memory module you are attempting to
read in the master port is defective or has no
valid data.

Press Menu now to return to the main menu.
Exchange the memory module in the master
port.

NAME EXISTS!

Defective memory module programmer.

Contact Rockwell Automation Technical
Support.

MEMORY FULL

The internal memory of the memory module
programmer is full.

Contact Rockwell Automation Technical
Support.