12 Bulletin 2097 Memory Module Programmer

Publication 2097-QS001D-EN-P - November 2011

4. Press

.

Shows the parameter version that the memory module programmer is configured for.
For example, 400.

INTERN CFG 400

5. Press

.

This function is not available for Bulletin 2097 memory modules.

F

ILES: 1

6. Press

.

The current voltage level of the four internal batteries is displayed. To guarantee safe operation,
the battery voltage must not fall below 3.6V DC.

B

ATTERY: 5.8VDC

7. Press .

The set password for the access protection (factory setting: 0000) is displayed. Entering and
changing has no effect on the use of Bulletin 2097 memory modules.

P

ASSWORD: 0000

8. Press .

Returns to the main menu.

MISCELLANEOUS

Step

Display

MENU