Rockwell Automation FactoryTalk Historian Classic for Batch User Guide User Manual
Page 46
Chapter 3 Collecting Batch Data
linked to a given batch. Only one deviation is created per parameter
or report, for the most severe limit violation. For example, if a
parameter has a verification method of HH/LL and the value
exceeds both the high and high-high limits, only one deviation event,
will be created for the high-high limit.
Column
Datatype Description
Example
uniqueid
text
Unique (create) ID
31
area
text
Area
THE_PAINT_COMPANY
starttime
date/time
Time stamp
2002-03-01 12:21:17.000
batchid
text
Batch ID
BATCH_ID-030102-3
EU
text
Engineering units
Gallons
unit
text
Unit name
REACTOR_1
phase
text
equipment module name
PHASE11
event
text
Batch event from the event
journal: Recipe Parameter
Deviation or Report
Parameter Deviation
Recipe Parameter Deviation
descript
text
Name of the parameter or
report that has exceeded
limits.
REPORT_10
esignatureid
integer
Unique electronic signature
number.
1
deviatedvalue
text
Actual value of the
parameter deviation.
101
targetvalue
text
Value of the target
parameter. The target
parameter is the recipe
parameter used in
calculating the limit when
the calculation method is
Percent or Relative.
100
limitviolated
text
Level of limit that was
violated: High/Low,
High-High/Low-Low, or
High-High-High/Low-Low-L
ow.
High/Low
limitvalue
text
Value of the limit that was
violated.
10
46
Rockwell Automation Publication BHIST-UM011A-EN-E-June 2014