FLEX Ex Redundant ControlNet Barrier Module 17

Publication

1797-5.35 - July 2004

Certification Specific ControlNet Ex System Diagrams

The following pages include certification specific ControlNet Ex system
diagrams and notes pertaining to these diagrams. Select either CENELEC,
UL, C-UL, or FM and follow the requirements of that diagram as you
configure and install your system.

CENELEC Installation Label

A label with this system marking must be attached near the main components
of the system. If the system is installed in a cabinet, this label must be fixed
inside the cabinet.

CENELEC Information

The isolator type 1797-BCNR/* is an associated apparatus according to
EN 50020. If the isolator is connected to intrinsically safe circuits the
applicable national local construction, installation and operating regulations
must be heeded (for example, Germany DIN EN 50020, DIN VDE 0165).

0102

ControlNet Ex System

Allen-Bradley

Attention!
Avoid electrostatic charging!

-20

0

C <= Ambient Temperature <= +70

0

C

1 Allen-Bradley Dr.
Mayfield Hts., OH USA

DMT 99 ATEX E 065 X
II (1) 2G SYST EEx ia/ib IIB/C T4