2 bus error – Rockwell Automation 61C501 AutoMax/AutoMate 115V Input Module User Manual
Page 21

5Ć3
5.2
Bus Error
Problem: A 31" or 50" through 58" appears on the Processor
module's LED in DCS5000/AutoMax systems. In AutoMate systems,
a 1" appears in any bit location if register 3764 of an AutoMate 30 or
register 17564 of an Automate 40. This error message indicates that
there was a bus error when the system attempted to access the
module. The possible causes of this error are a missing module, a
module in the wrong slot, or a malfunctioning module. It is also
possible that the user is attempting to write to registers on the
module. Refer to the instruction manual for the Processor module in
the rack for more information. Use the following procedure to isolate
a bus error:
Step 1.
Verify that the input module is in the correct slot and, for
DCS5000/AutoMax systems, that the I/O definitions are
correct.
Verify that the slot number being referenced agrees with
the actual slot number of the module. In DCS
5000/AutoMax systems, this module's register number is
always zero. Verify that the bit number refers to the proper
bit. Note that the bit number and wire number are not the
same.
For remote I/O installations, (DCS5000/AutoMax systems
only) also verify that the master slot and remote drop
number are defined correctly.
Step 2.
Verify that the module can be accessed.
Connect the programming terminal to the system and run
the ReSource Software. Use the MONITOR I/O function to
display register 0 in DCS5000/AutoMax systems. In
AutoMate systems, use the POINT MONITOR function to
display the point. If the programmer is able to monitor the
inputs, the problem lies in the application software
(proceed to step 3). If the programmer cannot monitor the
inputs, the problem lies in the hardware (proceed to
step 4).
Step 3.
Verify that the user application program is correct.
This module cannot be written to. If a BASIC task caused
the bus error, the error log will contain the statement
number in the task where the error occurred. If a Ladder
Logic or Control Block task caused the error, you will need
to search the task for any instances where you used an
input as a ladder logic coil or wrote to it in a control block
task.
In AutoMate systems, search the task for any instances
where you used an input as a coil.
Step 4.
Verify that the hardware is working correctly.
Verify the hardware functionality by systematically
swapping out the input module, Processor module(s), and
backplane. If the problem is not corrected after each
swap, replace the original item before swapping out the
next item.
For remote I/O installations (DCS5000/AutoMax systems
only), systematically swap out the input module, the slave
remote module, and the backplane. After each swap, if the
problem is not corrected, replace the original item before
swapping out the next item.