3 use in automate systems – Rockwell Automation 61C501 AutoMax/AutoMate 115V Input Module User Manual
Page 17

4Ć3
4.2.3
Restrictions on Use in DCS 5000/AutoMax
Systems
This section describes limitations and restrictions on the use of this
module in DCS 5000/AutoMax systems.
The 115V AC/DC Input module is a read only module. Attempts to
write to it will cause a bus error (severe system error). The following
are examples from programs that write to the module and should
therefore be avoided:
a. Referencing the module from a coil in a ladder logic task.
b. Referencing the module on the left side of an equal sign in a LET
statement in a control block or BASIC task.
c. Referencing the module as an output in a control block function.
4.3
Use In AutoMate Systems
In AutoMate systems, the 115V AC/DC Input module is accessed
using the MOVMR instruction block. This block reads the data from
the module and places it into a destination register, which,
depending upon the register chosen, can then be accessed as a
register or as a register and as individual bits. Note that the module
cannot be used in a remote rack in AutoMate systems.
Register 3765 in an AutoMate 30 Processor and register 17565 in an
AutoMate 40 Processor indicate whether there is a missing or
improperly seated module in the rack. The slots in the rack
correspond to the bits in the register, which are set to 1 (on) when a
module is missing or seated improperly. A set bit in either register
3765 or 17565 will not, however, affect the execution of the
application program.
4.3.1
Ladder Diagram Example
The following sample MOVMR instruction block is used to access a
115V AC/DC input module located in slot 4 of an AutoMate rack that
contains an AutoMate 30 Processor. The data from the module will be
stored in register 2000.
40
.00
76
.00
EN
EN
MOVMR
LENGTH:
ADDRS:
I/O-M:
B,H,W,S:
DEST:
VALUE:
1
400000
M
S
2000
Note that the coil address shown in the example is not valid for an
AutoMate 40 Processor.