4Ć8

For processors that do not support the AIN and AOUTblocks, you

can use the MOVE block to move data in and out of the registers

assigned and to determine the channel select bits. OverĆrange and

underĆrange bits should be used as inputs to error coils. The I/O

update will occur automatically at the end of each scan. See

Appendix C for a sample AutoMate program that writes to and reads

from the Analog Rail module without using AIN and AOUTblocks.

4.1.3

AutoMate Programming in Local Head Mode

In Local Head mode, the module is imaged in four I/O registers of

the processor. Data from all four channels is always available and

will be updated at the end of each scan. For input channels, it is not

necessary to select the channel. After the I/O update, the register

contains the data in the format shown in figure 4.9. For output

channels, the data in the register must be in the format shown in

figure 4.10 prior to the I/O update.

17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0

Octal

12 bits of converted analog data
overĆrange (1=overĆrange)
underĆrange (1=underĆrange)
not used

not used

Figure 4.9 Ć Local Head Mode Register Image for Input Channels

17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0

Octal

12 bits of analog output data
not used

not used
not used

not used

Figure 4.10 Ć Local Head Mode Register Image for Output Channels

The Analog Rail module data may also be accessed in the middle of

the scan (as opposed to the end of the scan) using the appropriate

number of Analog In (AIN) and Analog Out (AOUT) blocks. The AIN

block will set the overĆrange or underĆrange bits if applicable. See

section 4.1.4 for more information about the AIN and AOUTblocks.
Note that the AIN and AOUTblocks are supported by the AutoMate

20E (M/N 45C224 and 45C225), but not the AutoMate 20 (M/N

45C20, 45C21, 45C220, 45C221) by APX Version 3.0.