For DCS 5000, AutoMax, or Distributed Power DĆC Drive

systems, use the DCS 5000 or AutoMax Programming

Executive software I/O Monitor function, respectively. Test

output channels by writing a value between 0 and 4095 to

those channels and using an ammeter to verify that the

signal on the terminal points (4Ć20mA) is proportional. To

test input channels, verify that the input signal in the

channel (4Ć20mA) is proportional to an ammeter reading

at the terminal points.