Remove the ground wires on 2099-bm09-s, Mov cm cap – Rockwell Automation 2099-BMxxx Kinetix 7000 High Power Servo Drive Installation Instructions User Manual
Page 6

6 Kinetix 7000 High Power Servo Drives
Rockwell Automation Publication 2099-IN003B-EN-P - August 2013
Remove the Ground Wires on 2099-BM09-S and 2099-BM10-S Drives
The common mode capacitor ground wire is indicated by callout 3 and the MOV/input filter
cap ground wire is indicated by callout 4.
Remove the Ground Wires on 2099-BM11-S and 2099-BM12-S Drives
The common mode capacitor ground wire is indicated by callout 5 and the MOV ground wire is
indicated by callout 6.
IMPORTANT
You must remove the DC-DC converter and drive top cover to access and remove the common
mode capacitor ground wire. Refer to the Kinetix 7000 DC-DC Converter and Control Board
Kits Installation instructions, publicatio
.
WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY
POWER TERMINAL RATINGS
WIRE RANGE: 6-1/0 AWG (16-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)
GROUND TERMINAL RATINGS (PE)
300 VDC EXT PWR SPLY TERM (PS+, PS-)
WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)
17
21
INPUT AC
OUTPUT
Optional
Communications
Module
9
CM Cap - Older Drives
CM Cap - Newer Drives
MOV
MOV/Input
Filter Cap
3
3
4
4
U
T1
V
T2
W
T3
R
L1
S
L2
INPUT
OUTPUT
T
L3
PE
PE
PE
PE
MOV
CM Cap
DO NOT REMOVE
6
5