Set the Ground Jumper
Use the following table and illustrations to set the ground jumpers/wires for ungrounded power.
Jumper/Wire Location and Removal Instructions
Remove the Ground Wires on 2099-BM06-S, 2099-BM07-S, and 2099-BM08-S Drives
The common mode capacitor jumper is indicated by callout 1 (PE A) and the MOV jumper is
indicated by callout 2 (PE B).
Drive Cat. No.
Jumper/
Wire
Callout No.
Component
Protected
Description
2099-BM06-S
2099-BM07-S
2099-BM08-S
PE A
Common mode
capacitor
Remove the two jumpers above the power terminal
block. Refer to
2099-BM06-S, 2099-BM07-S, and 2099-BM08-S Drives
on page 5
PE B
MOVs
2099-BM09-S
2099-BM10-S
Green/yellow
wire
Common mode
capacitor
Remove DC-DC converter and drive top cover, and
disconnect the green/yellow wire from the drive
chassis. Insulate and secure the wire to prevent
unintentional contact with the chassis or components.
Refer to
Remove the Ground Wires on 2099-BM09-S
and 2099-BM10-S Drives on page 6
.
MOVs/
input filter cap
Disconnect the green/yellow wire next to the power
terminal block. Insulate and secure the wire to prevent
unintentional contact with the chassis or components.
Refer to
Remove the Ground Wires on 2099-BM09-S
and 2099-BM10-S Drives on page 6
.
2099-BM11-S
2099-BM12-S
Green/yellow
wire
Common mode
capacitor
Disconnect the two green/yellow wires from the PE
terminals on the power terminal block. Insulate and
secure each of these wires to prevent unintentional
contact with the chassis or components. Refer to
Remove the Ground Wires on 2099-BM11-S and
2099-BM12-S Drives on page 6
MOVs
1
2
3
4
5
6
BR1 BR2 DC+ DC- U/T1 V/T2 W/T3 R/L1 S/L2
T/L3
PE B
PE A
75C Cu Wire
3 AWG [25MM
2
] Max.
16 IN. LBS.
1.8 N-M
} TORQUE
WIRE
STRIP
CONTR
OL
PO
WER
AUX IN
+ –
SHLD
SHLD
PE
75C Cu Wire
6 AWG [10MM2] Max.
BR1 BR2
12 IN. LBS.
1.4 N-M
} TORQUE
PE A
PE B
CM Cap
MOV
Two Jumpers
PE A and PE B
Important: Do not discard or replace the grounding hardware.
1
2