Noise zones for kinetix 6000 drives – Rockwell Automation 2090-SRxxx External Shunt Modules Installation Instructions User Manual
Page 7
![background image](/manuals/580269/7/background.png)
Publication 2090-IN004B-EN-P — June 2008
External Shunt Modules 7
Noise Zones for Kinetix 6000 Drives
Observe these guidelines when mounting your external shunt module
outside the enclosure:
•
Mount circuit components and wiring in the very dirty zone or
in an externally shielded enclosure. Run shunt DC-bus and fan
wiring inside metal conduit to minimize the effects of EMI and
RFI.
•
Mount resistors (other than metal-clad) in a shielded and
ventilated enclosure outside the cabinet.
•
Keep unshielded wiring as short as possible. Keep shunt DC-bus
wiring as flat to the cabinet as possible.
•
Route thermal switch and fan wires separate from shunt DC-bus.
External Shunt Module Mounted Outside the Enclosure
C
D
D
D
D
D
VD
C
VD
D
1394 Digital Servo Controller
300W Shunt Module
BULLETIN 1394 300W SHUNT MODULE
ALLEN-BRADLEY
FOR USE WITH 1394-SJT22-X SYSTEM MODULE
CAT.
PART
SER.
INPUT DC
INPUT AC
FOR FUSE REPLACEMENT USE:
BUSSMAN CAT. NO.
R
(1)
Line Interface Module
Kinetix 6000
Drive System
Dirty Wireway
Clean Wireway
Motor Power Cables
Very Dirty Connections Segregated
(not in wireway)
Customer-supplied
Metal Enclosure
150 mm (6.0 in.)
clearance, min on all four
sides of the shunt module.
Enclosure
2094-BSP2
Shunt Module
Shunt DC-bus Wiring Methods:
Twisted pair in conduit (1st choice).
Shielded twisted pair (2nd choice).
Twisted pair, two twists per foot, min (3rd choice).
Metal Conduit
(where required
by local code)
I/O and Feedback Cables
Shunt Thermal Switch and Fan Wires (when present)
No sensitive
equipment within
150 mm (6.0 in.).
Route 24V DC I/O
shielded cable.
Route encoder/analog/registration
shielded cables.