External Shunt Module
Specifications
This section provides specifications for the Bulletin 1394 and Bulletin
2090 external shunt modules.
External Shunt Module Specifications
Environmental Specifications
External Shunt Module
Cat. No.
Drive
Voltage
V AC
Specifications
Bussmann
Replacement Fuse
Resistance
Range
Ω
Peak
Power
kW
Peak
Current
Amps
Cont.
Power
Watts
Shipping
Weight
kg (lbs)
1394-SR9A
230
(1)
4
41.0
101.25
300
3.63 (8)
FNQ-R-20-R1
460
160.0
200
FWP50A14F
1394-SR9AF
230
4
41.0
101.25
900
3.63 (8)
FNQ-R-20-R1
460
160.0
200
FWP50A14F
1394-SR36A
230
4
41.0
101.25
1800
8.6 (19)
FNQ-R-20-R1
460
160.0
200
FWP50A14F
1394-SR36AF
230
4
41.0
101.25
3600
9.0 (20)
FNQ-R-25-R1
460
160.0
200
FWP50A14F
2090-SR120-09
230
120-148
1.33 3.35
900 3.63
(8.0)
460
5.3
6.7 FWP-2.5A14F
2090-SR040-09
230
40-51
4.0 10.0
900 3.63
(8.0)
FNQ-R-2-R1
460
16.0 20.0
FWP-5A14F
2090-SR040-18
230
40-49
4.0 10.0
1800 8.6
(19.0)
FNQ-R-2-R1
460
16.0 20.0
FWP-6.3A14F
(1)
Requires the use of an FNQ fuse with an adapter to allow the smaller body fuse to fit the larger FWP fuse holder.
ATTENTION
The Bulletin 1394 and 2090 shunt modules ship with fuses
rated for 460V operation. For operation with drive systems
using 230V input power, you must replace the 460V shunt fuse
with a 230V fuse. Failure to observe this precaution could
result in equipment damage.
Attribute
Value
Ambient operating temperature
(1)
(1)
Power performance increases about 5.5 W for every 1°C (3.1 W/°F) drop in ambient temperature.
0…50 °C (32…122 °F)
Vibration
2g at 10…2000 Hz
Shock
15g 11 ms half sine
Altitude
1500 m (5000 ft)
Humidity
5…95% noncondensing