Processor Error Codes
Table B.C details some of the processor error codes. Refer to the Instruction Set
Reference Manual for a complete list of error codes and troubleshooting
information.
Table B.C
Processor Error Codes
Error Code
Cause
Corrective Action
0001
RAM program is corrupt
due to noise, lightning,
improper grounding or
loss of capacitor or batĆ
tery backĆup.
Check wiring, layout, grounding. If using a 4K
CPU, verify that a battery is installed to retain
RAM memory when power is removed. See
CPU FAULTĆFlashing under system LED status.
Restore the program using APS or an HHT.
0012
RAM program is corrupt
or RAM itself is bad due
to noise, lightning, imĆ
proper grounding, or
loss of capacitor or batĆ
tery backĆup.
Check wiring, layout, grounding. If using a 4K
CPU, verify that a battery is installed to retain
RAM memory when power is removed. See
CPU FAULTĆFlashing under system LED status.
Restore the program using APS or an HHT.
XX50, XX51, XX52
XX53, XX54, XX55
(xx = slot #)
I/O module configuraĆ
tion/conflict or runtime
problem.
Verify that processor configuration matches
your hardware by pressing F3 Offline Prg/Doc";
F1 Procssr Functns"; F1 Change Procssr"; F5
Configr I/O"; See CPU FAULTĆFlashing under
the system LED status.
XX56
(xx = slot #)
Chassis configuration
error.
Verify that chassis configuration in your program
matches your hardware by pressing F3 Offline
Prg/Doc"; F1 Procssr Functns"; F1 Change
Procssr"; F5 Configr I/O". If multiple chassis
system, verify proper installation of chassis inĆ
terconnect cable. See CPU FAULT Ć Flashing
under system LED status.