Editing the program with quick edit, Offline config – Rockwell Automation 9323-PA1E QUICK START GUIDE APS 6.0 User Manual
Page 47
Online Operations, Quick Edit
4–7
Editing the Program with Quick Edit
The quick edit feature of APS software allows you to move quickly from online
monitoring to offline editing, then back to online monitoring. To give you
experience at doing this, we will edit the program by adding an input instruction on
the rung. The effect of the edit: Selector switch 6 must be on (closed) to allow
pushbutton 0 to turn on pilot light 0.
We will place an XIC instruction in series with (to the right of) the XIC instruction
already entered. It will have address I:2/2, corresponding to selector switch 6 of the
demo unit. See the figure below.
( )
O:3
0
] [
I:1
0
] [
I:2
2
Add this instruction
Complete the following six steps to edit and test the edited program. The starting
point for this procedure is the online monitor file display, with the processor in the
run mode:
Press a function key
(file 2, rung 0)
REM RUN
no forces
PROC Addr 1
F2
CONFIG
DISPLAY
F9
FORCE
END
F10
EDIT
F3
EXIT
F6
F7
SEARCH
GENERAL
UTILITY
( )
O:3
0
] [
I:1
0
Input pushbutton turns on output pilot light
F8
DATA
MONITOR
F1
CHANGE
MODE
F5
DOCUMNT
1.
Go offline and edit the disk version of the file.
Press
CONFIG
OFFLINE
CONFIG
EDIT
F10
, then
CONFIG
OFFLINE
CONFIG
OFFLINE
DISK
F3
. Note that the status line of the display now
indicates that you are offline, at file GETSTART.