Troubleshooting
B–3
Table B.A
APS Error Messages (continued)
Error Message
Possible Causes
Corrective Action
I/O Address Not
Configured
Processor/system
configuration does not
match entered
addresses
Verify correct address format (I:slot/terminal
or O:slot/terminal); verify system configuration
by pressing F3 Offline Prg/Doc"; F1 Procssr
Functns"; F1 Change Procssr"; F5 Configr
I/O".
No Matching Disk File
Found
Processor program
does not exist on hard
disk
To read the processor program (upload),
press F8 Yes"; otherwise press F10 No" to
continue with other online activities.
No Memory Left or Not
Enough Memory to
Load Communication
Driver
PC does not have
enough free RAM
memory to continue
Verify your PC has >250K of free RAM to
execute APS. (>369K free RAM is required if
you are running the INTERCHANGE
software). Exit APS and type CHKDSK" at
DOS prompt. The last line should read
>250K bytes free" (or >369K). If not, disable
TSR, drivers, menus, shells, etc. loaded in
AUTOEXEC.BAT or CONFIG.SYS that may
be running in background. ReĆboot PC.
Incompatible
Processor Type
The processor
configuration of the
program you are
restoring does not
match your hardware
Verify that processor configuration of your
program matches your hardware by pressing
F3 Offline Prg/Doc"; F1 Procssr Functns; F1
Change Procssr".