12 High-bright Display Modules

Publication 2711P-IN026E-EN-P - September 2008

Mount the Terminal in a Panel

Four mounting clips secure the terminal to the panel.

Follow these steps to mount the terminal in a panel.

1. Cut an opening in the panel by using the panel cutout shipped with the

terminal.

2. Make sure the terminal sealing gasket is properly positioned on the terminal.

This gasket forms a compression type seal. Do not use sealing compounds.

3. Place the terminal in the panel cutout.

ATTENTION

Disconnect all electrical power from the panel before making the panel cutout.

Make sure the area around the panel cutout is clear.

Take precautions so metal cuttings do not enter any components already installed in
the panel.

Failure to follow these instructions may result in personal injury or damage to panel
components.

Sealing Gasket