Specifications – Rockwell Automation 1792D-12BT4PE ArmorBlock MaXum 12 In/4 Out Module with Ground Lug User Manual
Page 15

ArmorBlock MaXum 12 Input/ 4 Output Module With Ground Lug 15
Publication
1792D-IN056A-EN-P - October 2004
The following table describes individual I/O status indicators.
Specifications
I/O Status Indicators
Function Module Status
Indicator
Point
Indicator
1
Status
Outputs
Green
Green
Module Status blink red
Module Status blink red
Module Status blink red
Module Status blink red
None
Yellow
Orange
Red
Orange
Red
Output not energized
Output energized
Output shorted - auto restart
Output shorted - latching
Output no load - auto restart
Output no load - latching
Inputs
Green
Green
Module Status blink red
Module Status blink red
None
Yellow
Red
Blink red
No valid input
Valid input
Short on input connection
1
Off wire on input connection
1
1
Only the first LED of each input connector will light as red when twin inputs are used.
12 Input / 4 Output Module - Cat. No. 1792D-12BT4PE
Input Specifications
Maximum
Minimum
Inputs per block 12 - 3 wire or dry contact PNP devices or 6 - 4 wire PNP devices
Sensor Source Current (per input)
See the graph located after this Specifications table.
Off-wire Sense Current
0.5mA
-
On-state Voltage
25V dc
10V dc
On-state Current
10mA
2mA
Off-state Voltage
5V dc
-
Off-state Current
-
1.5mA
Output Specifications
Maximum
Minimum
Outputs per block 4 sourcing outputs labeled O0 through O3
Off Peak Blocking Voltage
30V
10V
On-state Voltage Drop
1V
-
On-state Current
2.0A
-
Off-state Leakage
1.5mA
-
Module Current (all outputs)
4.0A
-