Communicate with your armorblock maxum i/o module – Rockwell Automation 1792D-12BT4PE ArmorBlock MaXum 12 In/4 Out Module with Ground Lug User Manual
Page 10

10 ArmorBlock MaXum 12 Input/ 4 Output Module With Ground Lug
Publication
1792D-IN056A-EN-P - October 2004
Communicate With Your ArmorBlock MaXum I/O Module
This ArmorBlock module’s I/O is exchanged with the master through
a cyclic, poll, or change-of-state connection.
The module consumes and produces I/O data as follows:
Cyclic - allows configuration of the block as an I/O client. The block
will produce and consume its I/O cyclically at the rate configured.
Polled - a master initiates communication by sending its polled I/O
message to the module. The 12 input / 4 output module consumes
the message, updates outputs, and produces a response. The
response has input data, input faults, output faults, and the status of
the auxiliary power.
Change-of-State - productions occur when an input changes or a
fault condition occurs. If no input or fault condition change occurs
within the expected packet rate, a heartbeat production occurs. This
heartbeat production tells the scanner module that the
I/O module is alive and ready to communicate. Consumption occurs
when data changes and the master produces new output data to the
I/O block.
Refer to the table below for the word/bit definitions.
Type of I/O Connections
Consumes
Produces
Cyclic
1 Byte
4 Bytes
Polled
1 Byte
4 Bytes
Change-of-State
1 Byte
4 Bytes
Bit
07
06
05
04
03
02
01
00
Produces 0
I7
I6
I5
I4
I3
I2
I1
I0
Produces 1
ISC-D
ISC-C
ISC-B
ISC-A
I11
I10
I9
I8
Produces 2
OW-F
OW-E
OW-D
OW-C
OW-B
OW-A
ISC-F
ISC-E
Produces 3
RSVD
OPWR
RSVD
RSVD
OFLT3
OFLT2
OFLT1
OFLT0
Consumes 0
RSVD
RSVD
RSVD
RSVD
O3
O2
O1
O0
Where: I = Input, ISC = Input Short Circuit in Sensor Source Voltage, OW = Off Wire,
RSVD = Reserved, OPWR = Output Power (auxiliary power), OFLT = Output fault, O = Output