Rockwell Automation 1792D-12BT4PE ArmorBlock MaXum 12 In/4 Out Module with Ground Lug User Manual
Installation instructions
Publication
1792D-IN056A-EN-P - October 2004
Installation Instructions
ArmorBlock MaXum 12 Input/
4 Output Module With Ground Lug
Cat. No. 1792D-12BT4PE
This ArmorBlock MaXum I/O module (Cat. No. 1792D-12BT4PE) is
a stand-alone 24V dc I/O product, which communicates via a
DeviceNet network. The sealed housing of this module requires no
enclosure.
This module has 12 inputs and 4 outputs accessed through Y splitter
cables. Inputs are 24V dc devices. Four self-protected 24V dc outputs
can provide up to 2.0 amp each. Diagnostic features are short circuit,
open wire and no load detection reported to the connector level for
inputs and to point level for outputs. Local logic control has been
included.
An external lug exists to ground the block
.
43881
Ground lug
Document Outline
- ArmorBlock MaXum 12 Input/ 4 Output Module With Ground Lug
- Package Contents
- Install Your ArmorBlock MaXum I/O Module
- Set the Node Address
- Mount the Module to the Cable Base
- Connect the Input / Output Cord Sets to the MaXum Module
- Communicate With Your ArmorBlock MaXum I/O Module
- Troubleshoot With the Indicators
- Specifications
- North American Hazardous Location Approval
- Back Cover