Ac output modules – Rockwell Automation 1746-XXXX SLC 500 Digital I/O Modules Installation Instructions User Manual
Page 36
![background image](/manuals/579963/36/background.png)
36 SLC 500 Digital I/O Modules
Publication 1746-IN027D-EN-P - December 2012
AC Output Modules
Specifications – 1746-IH16
Attribute
Value
(1)(2)(3)
Voltage category
125V DC signal input (sinking)
Number of inputs
16
Points per common
16
Voltage, operating
Range:
90...146V DC
Points ON Simultaneously, max:
6 @ 146V DC and 30 °C (86 °F)
12 @ 146V DC and 50 °C (122 °F)
14 @ 132V DC and 55 °C (131 °F)
16 @ 125V DC and 60 °C (140 °F)
Backplane current
consumption
5V DC
0.085 A
24V DC
0.0 A
Signal delay, max
On = 9 ms
Off = 9 ms
Off-state voltage, max
20.0V DC
Off-state current, max
0.8 mA
Input current, nom
2.15 mA @ 125V DC
2.25 mA @ 132V DC
(1)
Removable terminal block.
(2)
Use ID Code 0507 when configuring your system with programming software or the HHT.
(3)
If the input module is connected in parallel with an inductive load, use surge suppression across the load to protect
the input module from damage caused by reverse voltage. Refer to the SLC 500 Modular Hardware Style User
Manual, publication
Specifications – 1746-OA8, 1746-OA16, and 1746-OAP12
Attribute
Value
1746-OA8
1746-OA16
(5)
1746-OAP12
(5)(6)(7)
Voltage category
120/240V AC signal input
Number of outputs
8
16
12
Points per common
4
8
6
Voltage, operating
85...265V AC @ 47...63 Hz
Backplane current
consumption
5V DC
0.185 A
0.370 A
0.370 A
24V DC
Signal delay, max resistive load
(1)
On = 1 ms
Off = 11.0 ms
Off-state leakage, max
(2)
2 mA