beautypg.com

Ac input modules – Rockwell Automation 1746-XXXX SLC 500 Digital I/O Modules Installation Instructions User Manual

Page 32

background image

32 SLC 500 Digital I/O Modules

Publication 1746-IN027D-EN-P - December 2012

AC Input Modules

Specifications – 1746-IA4, 1746-IA8, and 1746-IA16

Attribute

Value

1746-IA4

1746-IA8

1746-IA16

(2)

(2)

Removable terminal block.

Voltage category

100/120V AC signal input

Number of inputs

4

8

16

Points per common

4

8

16

Voltage, operating

85...132V AC @ 47...63 Hz

Backplane current consumption

5V DC

0.035 A

0.050 A

0.085 A

24V DC

0.0 A

Signal delay, max

On = 35 ms
Off = 45 ms

Off-state voltage, max

30V AC

Off-state current, max

2 mA

Input current

12 mA @ 120V AC, nom

Inrush current, max

(1)

(1)

An AC input device must be compatible with SLC 500 input circuit inrush current. A current limiting resistor can be used to limit
inrush current; however, the operating characteristics of the AC input-circuit will be affected.

0.8 A

Inrush current time duration, max

0.5 ms

Specifications – 1746-IM4, 1746-IM8, and 1746-IM16

Attribute

Value

1746-IM4

1746-IM8

1746-IM16

(2)

Voltage category

200/240V AC signal input

Number of inputs

4

8

16

Points per common

4

8

16

Voltage, operating

170...265V AC @ 47...63 Hz

Backplane current consumption

5V DC

0.035 A

0.050 A

0.085 A

24V DC

0.0 A

Signal delay, max

On = 35 ms
Off = 45 ms

Off-state voltage, max

50V AC

Off-state current, max

2 mA