Connect wiring to the field wiring arm – Rockwell Automation 1771-IXE Installation Instructions User Manual
Page 5

Thermocouple/Millivolt Input Module
5
Publication 1771Ć5.64 - October 1998
Connect your I/O devices to the cat. no. 1771-WI wiring arm
shipped with the module.
!
ATTENTION: Remove power from the 1771 I/O
chassis backplane and field wiring arm before
removing or installing an I/O module.
•
Failure to remove power from the backplane or
wiring arm could cause module damage, degradation
of performance, or injury.
•
Failure to remove power from the backplane could
cause injury or equipment damage due to possible
unexpected operation.
Input connections for the 1771-IXE/D are shown below.
+
+
–
–
1
Do not use - reserved for cold junction
compensation within wiring arm.
Short circuit
unused pins
Channel 1
Channel 2
18
Input 1 (+ lead)
17
Input 1 (- lead)
16
Input 2 (+ lead)
15
Input 2 (- lead)
14
Input 3 (+ lead)
13
Input 3 (- lead)
12
Input 4 (+ lead)
11
Input 4 (- lead)
10
Not Used
9
Not used
8
Input 5 (+ lead)
7
Input 5 (- lead)
6
Input 6 (+ lead)
5
Input 6 (- lead)
4
Input 7 (+ lead)
3
Input 7 (- lead)
2
Input 8 (+ lead)
1
Input 8 (- lead)
Terminal Identification
Terminal
Function
Wiring Arm
Cat. No. 1771-WI
Connect positive thermocouple leads
to even-numbered terminals, negative
leads to odd-numbered terminals.
Ground cable shield to I/O chassis
mounting bolt.
18
17
16
1
15
14
13
12
11
10
9
8
7
6
5
4
3
2
10527-I
The sensor cable must be shielded. The shield must:
•
extend the length of the cable, but be connected only at the 1771 I/O chassis
•
extend up to the point of termination
Important:
The shield should extend to the termination point, exposing just enough cable to
adequately terminate the inner conductors. Use heat shrink or another suitable
insulation where the wire exits the cable jacket.
Functional
Ground
Functional
Ground
Short circuit all unused channels by
connecting a jumper wire from the
+ terminal to the - terminal
Connect Wiring to the
Field Wiring Arm