Rockwell Automation 1784-PKTCS ControlNet PCI Scanner Card Installation Instrucitons User Manual
Page 62

A-6 Specifications
Publication 1784-IN042A-EN-P - April 2005
storage temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
-40 to 85
°C (-40 to 185 °F)
relative humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5 to 95% non-condensing
vibration
IEC 60068-2-6 (Test Fc, Operating):
2g @ 10-500Hz
operating shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30g
non-operating shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50g
emissions
CISPR 11:
Group 1, Class A
ESD immunity
IEC 61000-4-2:
6kV contact discharges
8kV air discharges
radiated RF immunity
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 80MHz to 2000MHz
10V/m with 200Hz 50% pulse 100%AM at 900MHz
10V/m with 200Hz 50% pulse 100%AM at 1890MHz
EFT/B immunity
IEC 61000-4-4:
+/-2kV at 5kHz on communications ports
surge transient immunity
IEC 61000-4-5:
+/-2kV line-earth (CM) on communications ports
conducted RF immunity
IEC 61000-4-6:
10Vrms with 1kH sine-wave 80% AM from 150kHz to 80MHz
enclosure type rating
none (open-style)
power requirements
In US, this equipment must be powered from UL Listed Information
Technology Equipment or UL Listed Industrial Control Equipment. In
Canada, this equipment must be powered by an SELV source, CSA
Certified Information Technology Equipment, or CSA Certified
Process Control Equipment.
5V dc, 700mA maximum, Class 2
power dissipation
3.5W
isolation voltage (continuous-voltage
withstand rating)
50V continuous
Tested to withstand 500V for 60 seconds.