Rockwell Automation 1784-PKTCS ControlNet PCI Scanner Card Installation Instrucitons User Manual
Page 46

5-6 Once You Have Completed the Installation
Publication 1784-IN042A-EN-P - April 2005
RSNetWorx for ControlNet 6.00.00 or later is required to display these error messages. If
RSNetWorx for ControlNet 5.11.00 is used, “Unknown Error” will be displayed on the
Connection Status tab of the scan list configuration screen.
Resolve the Errors
Follow this procedure to resolve error conditions on the PC containing the 1784-PKTCS card
reporting the error:
1. Start the controlling application.
2. Verify that the size of the output data provided by the controlling application is as
large as the output data configured in the scan list of the 1784-PKTCS card.
3. Verify that the controlling application has written the output data at least once.
Shut Down the Controlling Application Before You Download a Configuration to the
Network or Modify the Scan List
You cannot modify or delete scan list entries of the 1784-PKTCS card that correspond to
connections being controlled by your application.
• If you attempt to download a configuration to your network and connections are
being controlled by your application, RSNetWorx for ControlNet displays the
following screen:
If you see this screen, you should:
– Shut down the application that is controlling the connections.
– Use RSNetWorx to download the configuration to your network.