Install the Components
1. Determine an adequate mounting location for the tap. Refer to the dimension
drawing shown below.
2. To mount the tap to the DIN rail, use the hardware provided in the kit and attach as
shown in the following illustration.
3. To mount the tap through an enclosure wall, drill a hole of approximately 17.2 mm
for the 1786-TNCJI4 isolated bulkhead connector.
ATTENTION
Do not over-tighten the screws. Over-tightening the screws can
damage the tap. The applied torque should be 0.2-0.4 N-m (1-2
ft.-lbs).