ControlNet IP67 Tap and Cable Assembly Kit Installation Instructions 13
Publication 1786-IN017B-EN-P - May 2004
e. Inspect the heat-shrink tubing to ensure that there are no voids where the glue has
incompletely melted. Voids could cause a loss of the IP67 rating.
2. Attach the trunk line to the tap. Tighten the trunk-line connector to 1 N-m (0.74
ft.-lbs.).
IMPORTANT
Be sure to install the dust cap on any unused connectors. Doing so will:
•
prohibit the center conductor or the outer conductor from
inadvertently shorting to ground during installation
•
provide partial environmental protection if a tap is left disconnected
for a prolonged time
31297-M
Place the tubing against
the shoulder of the TNC
connector
Ensure that there are no
voids where glue has
incompletely melted