Assembly objects and connections – Rockwell Automation 1788-EN2DNR EtherNet/IP to DeviceNet Linking Device User Manual User Manual
Page 31
![background image](/manuals/579864/31/background.png)
Rockwell Automation Publication 1788-UM059A-EN-P - August 2014
31
Configure the Linking Device
Chapter 3
Assembly Objects and Connections
Three Assembly Object instances are accessible from the EtherNet/IP network:
input, output and status. The input and output assemblies are linked to the input
and output tags created in the Studio 5000 environment. The status assembly
provides current status information about the linking device.
The assembly instances associated with these three assemblies are listed in the
following tables.
Input Assembly
The input assembly contains a 32-bit status register followed by the data in the
linking device’s input data table.
The input data format and content is determined by the DeviceNet scanner
configuration. The data appears in the table as it is mapped from the DeviceNet
input connections. The input data in the assembly is 124 DINTs long; however,
only the size of the input data table is used. The remaining space is filled with the
value 0 (zero).
Output Assembly
The output assembly contains a 32-bit command register followed by the data in
the linking device’s output data table.
The output data format and content is determined by the DeviceNet scanner
configuration. The data appears in the table as it is mapped to the DeviceNet
output connections. The output data in the assembly is 123 DINT long;
however, only the size of the output data table is used. The remaining space is
ignored.
IMPORTANT
With a specific 1788-EN2DNR profile, I/O tags are mapped without an offset.
For example, the Logix Designer application input tag EN2DNR:I:Data[0]
corresponds to word 0 of the RSNetWorx for DeviceNet software input mapping
table.
Input Assembly Format
DINT
Offset
Size in DINTs
Description
Studio 5000 Environment Version 21or Later
Example Tags
0
1
Status register
EN2DNR:
I.Status Register
1
Up to 123
Input data
EN2DNR:
I.Data[0 …123]
Output Assembly Format
DINT
Offset
Size in DINTs
Description
Studio 5000 Environment Version 21or Later
Example Tags
0
1
Command register
EN2DNR:O.CommandRegister
1
Up to 124
Output data
EN2DNR:O.Data[0 …122]