Chapter 2

Install the Linking Device

Connect the Linking Device
to the EtherNet/IP Network

Connect the EtherNet/IP network cable to either of the two RJ45 ports on the
front of the linking device.

Connect the Linking Device
to the DeviceNet Network

1. With power to the linking device off, connect the DeviceNet network

cable to the DeviceNet connector on the linking device.

The female terminal block connector is provided with the linking device.

RJ45 Ports

ATTENTION: Do not wire more than two conductors on any single terminal. To
comply with the CE Low Voltage Directive (LVD), this equipment must be
powered from a source compliant with safety extra low voltage (SELV) or
protected extra low voltage (PELV). To comply with UL restrictions, this
equipment must be powered from a source compliant with Class 2 or Limited
Voltage/Current.

TIP

The two 121 ? termination resistors that come with the linking device are
required for proper network termination at each end of the trunk line. See the
DeviceNet Specification (available from the Open DeviceNet Vendors
Association at

http://www.odva.org

) for specific rules on DeviceNet

connections and termination.

(Red) Net Power 24V DC

(White) CAN High +

CAN Shield

(Blue) CAN Low

(Black) Net Power 24V DC Common

31442-M