MicroLogix 1200 Isolated Relay Output Module 5

Publication 1762-IN017C-EN-P - May 2013

Mounting

Minimum Spacing

Maintain spacing from enclosure
walls, wireways, adjacent
equipment, etc. Allow 50.8 mm
(2 in.) of space on all sides for
adequate ventilation, as shown:

.

DIN Rail Mounting

The module can be mounted using the following DIN rails: 35 x 7.5 mm
(EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).

Before mounting the module on a DIN rail, close the DIN rail latch. Press the DIN rail
mounting area of the module against the DIN rail. The latch will momentarily open and lock
into place.

ATTENTION

!

Do not remove protective debris strip until after the module and all other
equipment near the module is mounted and wiring is complete. Once
wiring is complete and the module is free of debris, carefully remove
protective debris strip. Failure to remove strip before operating can cause
overheating.

TIP

1762 expansion I/O may be mounted horizontally only.

ATTENTION

!

During panel or DIN rail mounting of all devices, be sure that all debris
(metal chips, wire strands, etc.) is kept from falling into the module.
Debris that falls into the module could cause damage when power is
applied to the module.

Side

Side

Top

Bottom

MicroLogix

1200

176

2 I/O

176

2 I/O

176

2 I/O