Rockwell Automation 1762-OX6I MicroLogix 1200 Relay Output Module User Manual
Page 12

12 MicroLogix 1200 Isolated Relay Output Module
Publication 1762-IN017C-EN-P - May 2013
Certifications
Certification (when product is
marked)
(1)
(1)
See product certification link at
Certificates, and other certification details.
Value
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E322657
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S and Canada. See UL File E334470.
CE
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Autralian Rediocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
KC
Korean Registration of Broadcasting and Communications Equipment,
compliant with:
Article 58-2 of Radio Waves Act, Clause 3
Output Specifications
Specification
Value
Voltage Category
AC/DC Type C relay
Operating Voltage Range
5…265V AC
5…125V DC
Number of Outputs
6
Bus Current Draw (max.)
110 mA at 5V DC
110 mA at 24V DC
Heat Dissipation
2.8 W
Signal Delay (max.) -Resistive Load
(1)
On Delay: 10 ms (max.), 6 ms (typical)
Off Delay: 20 ms (max.), 12 ms (typical)
Off-State Leakage Current
0 mA
On-State Current
100 mA at 5V DC
(2)
Continuous Current per Point
7 A max. (See Relay Contact Ratings below.)
Continuous Current Per Module (max.)
See Module Load Ratings on page 14.
Power Supply Distance Rating
6