beautypg.com

Specifications – Rockwell Automation 1762-OX6I MicroLogix 1200 Relay Output Module User Manual

Page 11

background image

MicroLogix 1200 Isolated Relay Output Module 11

Publication 1762-IN017C-EN-P - May 2013

Specifications

General Specifications

Specification

Value

Dimensions, H x W x D

90 x 40 x 87 mm
height including mounting tabs is 110 mm
3.54 x 1.58 x 3.43 in.
height including mounting tabs is 4.33 in.

Approximate Shipping Weight
(with carton)

220 g (0.485 lbs.)

Temperature, nonoperating

-40…85 °C (-40 …185 °F)

Temperature, operating

0…55°C (-32…131°F)

Operating humidity

5…95% non-condensing

Operating altitude

2000 m (6561 ft)

Vibration

Operating: 10…500 Hz, 0.030 in. max. peak-to-peak
DIN Rail Mounting: N.O. 2.5G, N.C. 2.5G
Panel Mounting: N.O. 2.5G, N.C. 0.5G

Shock

Operating: 30 g

Module power LED

On: indicates power is applied.

Vendor ID Code

1

Product type code

7

Product code

124

Hazardous Environment Class

Class I, Division 2, Hazardous Location, Groups A, B, C, D
ISA/ANSI12.12.01
(C-UL under CSA C22.2 No. 213)

Noise Immunity

NEMA standard ICS 2-230

Radiated and Conducted Emissions

EN50081-2 Class A

Electrical /EMC:

The module has passed testing at the following levels:

ESD Immunity (EN61000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated Immunity (EN61000-4-3)

10 V/m, 80 to 1000 MHz, 80% amplitude modulation,

Fast Transient Burst (EN61000-4-4)

2 kV, 5 kHz

Surge Immunity (EN61000-4-5)

2 kV common mode, 1 kV differential mode

Conducted Immunity (EN61000-4-6)

10V, 0.15…80 MHz

(1)

(1)

Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to
1000 MHz.