1734-oe2c analog current output module, Product code: 0019h, Data map – Rockwell Automation 1734-APB Point I/O Profibus Adapter Module User Manual
Page 75: Configuration data, Diagnostic data, B-11, Product code: 0019h data map, Configuration data: diagnostic data
Publication 1734-UM005B-EN-P - June 2001
Default Data Maps B-11
1734-OE2C Analog Current
Output Module
Product Code: 0019h
Data Map:
Output size: 2 Word; Input size: 0 Word
Configuration Data:
Diagnostic Data
Possible Error Codes:
7
6
5
4
3
2
1
0
Produces (Rx)
Output Channel 0
Output Channel 1
Consumes (Tx)
No consumed data
7
6
5
4
3
2
1
0
Reserved
AD
R
IA
FA
Engineering Units Low (high byte)
Default value = 06h
Engineering Units Low (low byte) Default value = 66h
Engineering Units High (high byte)
Default value = 1Fh
Engineering Units High (low byte) Default value = FFh
Fault Value (high byte)
Default value = 00
Fault Value (low byte)
Default value = 00
Idle Value (high byte)
Default value = 00
Idle Value (low byte)
Default value = 00
Meaning of bits described below
FA = Fault Action
IA = Idle Value
Value
Definition
Value
Definition
0
Hold Last State
0
Hold Last State
1
Fault Value (default)
1
Idle Value (default)
R = Range
AD = Alarm Disable
Value
Definition
Value
Definition
0
4 to 20mA (default)
0
Enable (default)
1
0 to 20mA
1
Disable
Code
Error Type
6
Wire Break
16
Module incorrect or missing. Reported on channel 0, applies to whole module.