beautypg.com

1734-oe2c analog current output module, Product code: 0019h, Data map – Rockwell Automation 1734-APB Point I/O Profibus Adapter Module User Manual

Page 75: Configuration data, Diagnostic data, B-11, Product code: 0019h data map, Configuration data: diagnostic data

background image

Publication 1734-UM005B-EN-P - June 2001

Default Data Maps B-11

1734-OE2C Analog Current
Output Module

Product Code: 0019h

Data Map:

Output size: 2 Word; Input size: 0 Word

Configuration Data:

Diagnostic Data

Possible Error Codes:

7

6

5

4

3

2

1

0

Produces (Rx)

Output Channel 0

Output Channel 1

Consumes (Tx)

No consumed data

7

6

5

4

3

2

1

0

Reserved

AD

R

IA

FA

Engineering Units Low (high byte)

Default value = 06h

Engineering Units Low (low byte) Default value = 66h

Engineering Units High (high byte)

Default value = 1Fh

Engineering Units High (low byte) Default value = FFh

Fault Value (high byte)

Default value = 00

Fault Value (low byte)

Default value = 00

Idle Value (high byte)

Default value = 00

Idle Value (low byte)

Default value = 00

Meaning of bits described below

FA = Fault Action

IA = Idle Value

Value

Definition

Value

Definition

0

Hold Last State

0

Hold Last State

1

Fault Value (default)

1

Idle Value (default)

R = Range

AD = Alarm Disable

Value

Definition

Value

Definition

0

4 to 20mA (default)

0

Enable (default)

1

0 to 20mA

1

Disable

Code

Error Type

6

Wire Break

16

Module incorrect or missing. Reported on channel 0, applies to whole module.