beautypg.com

Rockwell Automation 1734-APB Point I/O Profibus Adapter Module User Manual

Page 48

background image

Publication 1734-UM005B-EN-P - June 2001

4-10 Communication and I/O Table Mapping

Structure of Slave_Diagnosis

Octet

Description

0

Station Status 1

1

Station Status 2

2

Station Status 3

3

Master PROFIBUS address

4

Identifier number (high byte)

5

Identifier number (low byte)

6

Module-related header byte

7-14

Module-related diagnostic block

15-17

1st channel-related diagnostic message

18-20

2nd channel-related diagnostic message

.

.

.

.

42-44

10th channel-related diagnostic message

IMPORTANT

The length of the diagnostic frame varies between 15
and 45 bytes since the length of the channel-related
part is dynamic in its structure.