A-2 Specifications

General Specifications

Indicators

3 red/green status indicators
Adapter status
PROFIBUS status
PointBus status
2 green power supply status indicators:
System Power (PointBus 5V power)
Field Power (24V from field supply)

Power Consumption

8.1W maximum @ 28.8V dc

Power Dissipation

2.8W maximum @ 28.8V

Thermal Dissipation

9.5 BTU/hr maximum @ 28.8V dc

Isolation Voltage

1250V rms/V ac

Field Power Bus

Nominal Voltage
Supply Voltage Range
Supply Current

24V dc
10-28.8V dc range,
10A maximum

Dimensions Inches

(Millimeters)

3.0H x 2.16W x 5.25L
(76.2H x 54.9W x 133.4L)

Environmental Conditions

Operational Temperature
Storage Temperature
Relative Humidity
Shock

Operating
Non-operating

Vibration

-10 to 55

o

C (14 to 131°F)

-40 to 85

o

C (-40 to 185°F)

5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6

Conductors Wire Size

Category

14 AWG (2.5mm

2

) - 22 AWG (0.25mm

2

) solid or stranded copper

wire rated @ 75°C or higher
3/64 inch (1.2mm) insulation maximum
2

1

Terminal Base Screw Torque

7 pound-inches (0.6Nm)

Field Wiring Terminations

PROFIBUS

1 - Not connected

6 - +5V Bus

2 - Not connected

7 - Not connected

3 - +RTX/TX data line 8 - Negative RTX/TX
4 - Request to send

9 - Not connected

5 - Ground Bus

Housing - Earth ground

Power Supply

0 - No Connection

1 - No Connection

2 - Chassis Ground

3 - Chassis Ground

4 - Common

5 - Common

6 - Supply

7 - Supply

Mass

9.0 oz/255 grams

Agency Certification (when
product is marked)

CE marked for all applicable directives
C-Tick marked for all applicable acts

1

Use this conductor category information for planning conductor routing as described in publication 1770-4.1, “Industrial

Automation Wiring and Grounding Guidelines.”