Troubleshoot the Processor System

Publication 1785-10.7 – October 1997

Indicator

Color

Channel Mode

Description

Probable Cause

Recommended Action

A or B

Green
(steady)

Remote I/O
Scanner

Active Remote I/O link, all
adapter modules are
present and not faulted

Normal operation

No action required

Remote I/O
Adapter

Communicating with
scanner

DH+

Processor is transmitting or
receiving on DH+ link

Green
(blinking
rapidly or
slowly)

Remote I/O
Scanner

At least one adapter is
faulted or has failed

Power off at
remote rack

Cable broken

Restore power to
the rack

Repair cable

DH+

No other nodes on network

Red
(steady)

Remote I/O
Scanner
Remote I/O
Adapter
DH+

Hardware fault

Hardware error

Turn power off, then
on.

Check that the
software
configurations match
the hardware set-up.

Replace the
processor.

Red
(blinking
rapidly or
slowly)

Remote I/O
Scanner

Faulted adapters detected

Cable not
connected or
is broken

Power off at
remote racks

Repair cable

Restore power to
racks

DH+

Bad communication on DH+

Duplicate
node detected

Correct station address

Off

Remote I/O
Scanner
Remote I/O
Adapter
DH+

Channel offline

Channel is not
being used

Place channel online if
needed