Troubleshoot the processor system, Chapter – Rockwell Automation 1785-L20C_L40C QUICK START CONTROLNET PLC-5 User Manual

Page 21

background image

Chapter

4

Publication 1785-10.7 – October 1997

Troubleshoot the Processor

System

If you want to read about:

See page:

Using the general status indicators

4-1

Using the ControlNet status indicators

4-3

Monitoring the ControlNet configuration and status screens

4-6

The general status indicators inform you of the general operational
state of the processor.

Indicator

Color

Description

Probable Cause

Recommended Action

BATT

Red

Battery low

Battery low

Replace battery within 10 days

Off

Battery is good

Normal operation

No action required

PROC

Green
(steady)

Processor is in run
mode and fully
operational

Normal operation

No action required

Green
(blinking)

Processor memory is
being transferred to
EEPROM

Red
(blinking)

Major fault

Run-time error

Check major fault bit in status file
(S:11) for error definition

Clear fault bit, correct problem,
and return to run mode

Alternating
Red and
Green

Processor in
FLASH-memory
programming mode

Normal operation if
processor’s FLASH
memory is being
reprogrammed

No action required – allow flash
update to complete

Processor FLASH
memory checksum
error

Contact your local A-B
representative for a field firmware
update

Red
(steady)

Major fault

Processor
memory has
checksum error

Memory
module error

Internal diagnostics
have failed

Clear memory and
reload program

Check backplane switch settings
and/or insert correct memory
module

Power down, reseat processor
and power up; then, clear memory
and reload your program. Replace
EEPROM with new program;
then, if necessary, replace
the processor

Off

Processor is in program
load or test mode or is
not receiving power

Check power supply
and connections

BATT

PROC

FORCE

COMM

Using This Chapter

Using the General
Status Indicators