beautypg.com

Rockwell Automation 1785-L20C_L40C QUICK START CONTROLNET PLC-5 User Manual

Page 24

background image

4–4

Troubleshoot the Processor System

Publication 1785-10.7 – October 1997

Indicator

Color

À

Probable Cause

Recommended Action

and

B

Off

Internal diagnostics failed

1.

Turn power off, make sure ControlNet
address is not 00, reseat processor, then
power up

A

B

power up

2.

Clear memory and reload your program

3.

Replace EEPROM with new program

4.

If still an error, replace the processor

No power

Check power supply

Steady
Red

Faulted unit

Cycle power or reset unit

If fault persists, contact your Allen-Bradley Company,
Inc. representative or distributor

Alternating
Red/Green

Self-test

No action required

Alternating
Red/Off

Incorrect node configuration

Check network address and other ControlNet
configuration parameters

Off

Channel disabled

No action required

or

B

O

annel i able

Configure for ControlNet communication

or

A

B

Steady
Green

Normal operation

No action required

Flashing

reen O

Temporary errors

No action required

la in

Green/Off

e

orar error

Make sure that ControlNet is properly terminated

The processor’s ControlNet address
is above UMAX

Configure the ControlNet network so that UMAX is at
least as high as the processor’s ControlNet address.

Set the processor’s ControlNet address at or below
UMAX.

Flashing
Red/Off

Media fault

Check media for broken cables, loose connectors,
missing terminators, etc.

e O

No other nodes present on network

Add other nodes to the network

Flashing

e

reen

Incorrect network configuration

Cycle power or reset unit

la in

Red/Green

ncorrect net or con i uration

If fault persists, contact your Allen-Bradley Company,
Inc. representative or distributor

À

Definition of terms:

alternating

the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together);

the two indicators are always in opposite states, out of phase

flashing

the indicator alternates between the two defined states (applies to each indicator viewed independent of the other); if both

indicators are flashing, they flash together, in phase

steady

indicator is on continuously in the defined state