Configuring Your Block I/O
Chapter 3
3-7
Table 3.B
1791ĆIOBW Input Terminal Addressing for Groups 0 and 1 (TRM1)
Terminal
Number
Input
Assignment
Group 0
Program
Address
Terminal
Number
Input
Assignment
Group 1
Program
Address
1
Common A
19
Common B
2
Input 00
1XY00
20
Input 00
1X(Y+1)00
3
Input 01
1XY01
21
Input 01
1X(Y+1)01
4
Input 02
1XY02
22
Input 02
1X(Y+1)02
5
Input 03
1XY03
23
Input 03
1X(Y+1)03
6
Input 04
1XY04
24
Input 04
1X(Y+1)04
7
Input 05
1XY05
25
Input 05
1X(Y+1)05
8
Input 06
1XY06
26
Input 06
1X(Y+1)06
9
Input 07
1XY07
27
Input 07
1X(Y+1)07
10
Input 10
1XY10
28
Input 10
1X(Y+1)10
11
Input 11
1XY11
29
Input 11
1X(Y+1)11
12
Input 12
1XY12
30
Input 12
1X(Y+1)12
13
Input 13
1XY13
31
Input 13
1X(Y+1)13
14
Input 14
1XY14
32
Input 14
1X(Y+1)14
15
Input 15
1XY15
33
Input 15
1X(Y+1)15
16
Input 16
1XY16
34
Input 16
1X(Y+1)16
17
Input 17
1XY17
35
Input 17
1X(Y+1)17
18
N.C.
36
N.C.
37
N.C.
Where:
X = Rack Number (1, 2, 3 ...)
Y = Module Group (0, 2, 4, 6)
Type of I/O
I/O Rack
Number
I/O Group
Number
I/O Bit
1 X Y 00
1 = Input
0 = Output
PLCĆ2 Example
Type of I/O
I/O Rack
Number
I/O Group
Number
I/O Bit
I
X Y 00
I = Input
O = Output
PLCĆ3, PLCĆ5, PLC5/250 Example