Installing block i/o chapter 2, Power supply requirements, Wiring requirements – Rockwell Automation 1791-I0VW USER MANUAL User Manual
Page 19: Wiring cable requirements are shown in table 2.f
Installing Block I/O
Chapter 2
2-8
Power Supply Requirements
An external 24V dc (+10/-25%) power supply is required to power the
block. Total current required to power the block is equal to 100mA.
In addition, the external power supply should have current limiting
capabilities. The voltage range must not exceed 18.0-26.4V dc.
Wiring Requirements
Wiring cable requirements are shown in Table 2.F.
Table 2.F
Acceptable Wiring Cables for Block I/O Connection
Use
Cable Type
With
Remote I/O Link
Belden 9463
PLCĆ2, PLCĆ3, PLCĆ5 family programmable
controllers and SLC controllers
Input and Output wiring
Up to 14AWG (2mm
2
)Stranded with
3/64 inch (1.2mm) insulation
All
Figure 2.3
Remote I/O Link Wiring
GROUP No.
GROUP No.
2
(CLR)
Shield
1
(BLU)
24VDC
RET
24VDC
Chassis
GND
10928ĆI
1
1
150 OHM
82 OHM
OFF
TERMINATION
RESISTOR
Connnection
1
(BLU)
2
(CLR)
Shield
Clear Wire
X
Blue Wire
X
Shield Wire
X