FLEX I/O 8 Output HART Analog Module 31

Publication

1794-IN109D-EN-P - January 2014

Environmental

Attribute

Value

Temperature,
operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20...55 °C (-4...131 °F)

Temperature,
nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

–40...85 °C (–40...185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

2 g @ 10...500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

15 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock):

15 g

Emissions

CISPR 11:

Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF
Immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80...2500 MHz

1V/m with 1 kHz sine-wave 80% AM from 2500...2700 MHz

EFT/B Immunity

IEC 61000-4-4:

±2 kV at 5 kHz on power ports

±2 kV at 5 kHz on signal ports

Surge Transient
Immunity

IEC 61000-4-5:

±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports

±2 kV line-earth(CM) on shielded ports

Conducted RF
Immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80%AM from 150 kHz...80 MHz