FLEX I/O 8 Output HART Analog Module 11

Publication

1794-IN109D-EN-P - January 2014

Ground the Module

All I/O wiring must use shielded wire. Shields must be terminated external to
the module, such as bus bars and shield-terminating feed-throughs.

Outputs

Each output can operate an analog field device.
The channels in these modules are electrically connected to each other and
have a common plus-line.

IMPORTANT

When interconnecting several lines, you must consider the total accumulated
power.

44862

43849

HART

Modem

1794-OE8H/B

Bus

uC

FlexBus

45

Ω

21.6 V

250

Ω

+V

-V

+

4...20 mA

sig

-

4...20 mA

F

I

Power Supply