Domain name service, Identify the module within a network, Save and restore programs – Rockwell Automation 1785-ENET PLC-5 Ethernet Interface Module Installation Instructions User Manual
Page 31

PLC-5 Ethernet Interface Module 31
Publication 1785-IN019B-EN-P - January 2007
Identify the Module Within a Network
The PLC-5 Ethernet Interface Module supports the Simple Network Management Protocol
(SNMP).
The module responds automatically to SNMP requests and maintains a management
information base (MIB) file (Level II). Information kept in this file could include:
• number of datagrams received.
• number of fragmented packets received.
• maximum number of TCP connections allowed.
Save and Restore Programs
You can physically and logically save and restore all programs, if you are using:
• any release of RSLogix 5 programming software.
• AI Programming Software, release 7.21 or later, for all logical saves/restores.
• 6200 Series Programming Software, release 5.2 or later, for all logical saves/restores.
• an enhanced PLC-5 controller, series B or later.
Domain Name Service
DNS allows an Internet Protocol (IP) address in symbolic form to be converted into the
equivalent numeric IP address. For the PLC-5 controller, this conversion is a service provided
by a remote host on the network.
F002
Incomplete address
F003
Incorrect address
F006
Addressed file does not exist in target controller
F007
Destination file is too small for number of words requested
F00A
Target controller cannot put requested information in packets
F00B
Privilege error, access denied
F00C
Requested function is not available
F00D
Request is redundant
F011
Data type requested does not match data available
F012
Incorrect command parameters
Code
(Hexadecimal - word 1 of
the control block)
Description
(displayed on the data monitor screen)