App a - specifications, Specifications, Appendix a – Rockwell Automation 1785-CHBM ControlNet PLC-5 Hot Backup System User Manual User Manual
Page 79: Appendix
![background image](/manuals/579490/79/background.png)
1
Publication 1785-UM024B-EN-P - January 2003
Appendix
A
Specifications
Specifications
The following specifications are for the 1785-CHBM cartridge.
Memory Module
1785-CHBM
Capacity
100K words
Type
Nonvolatile
Write Protection
By removing the jumper
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0-60
o
C (32–140
o
F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bc, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
–40 to 85
o
C (–40 to 185
o
F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating
Damp Heat):
5–95% non condensing
Vibration
IEC60068-2-6 (Test Fc, Operating):
2g @10–500Hz
Shock
IEC60068-2-27:1987, Test Ea (Unpackaged shock, ES#002)
Operating - 30g
Non-operating - 50g
Emissions
CISPR 11:
Group 1, Class A (with appropriate enclosure)
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80% AM from 30MHz to 1000Mhz
Processor Compatibility
1785-L20C15, -L40C15 or -L80C5
Weight
2.5 oz (7.88g)
Certifications
(when product is marked)
UL
UL Listed Industrial Control Equipment
CSA
CSA Certified Process Control Equipment
CSA
CSA Certified Process Control Equipment for Class I, Division 2 Group
A,B,C,D Hazardous Locations
CE
1
European Union 89/336/EEC EMC Directive, compliant with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
C-Tick
1
Australian Radiocommunications Act, compliant with:
AS/NZS 2064; Industrial Emissions
1
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.