Using the 1785-chbm cartridge status indicators, Using the 1785-chbm cartridge status indicators -3 – Rockwell Automation 1785-CHBM ControlNet PLC-5 Hot Backup System User Manual User Manual
Page 67
![background image](/manuals/579490/67/background.png)
Publication 1785-UM024B-EN-P - January 2003
Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup System 5-3
Using the 1785-CHBM
Cartridge Status Indicators
The 1785-CHBM cartridge status indicators indicate the operational
state of the ControlNet PLC-5 backup system. The following table lists
the various LED states and the recommended action:
LED
Color
Indicates
Probable Cause
Corrective Action
PRI
Green
This processor is the primary (i.e., it controls the
outputs).
Normal operation
No action required
Green blinking
This processor is in the Lonely Primary backup
state
No good scheduled
connections
Check media for broken cables,
loose connectors, missing
terminators, etc.
Red
The backup system is not yet completely
configured (i.e., system is in the Invalid backup
state).
Improper backup
configuration
parameters
Improper ControlNet
Backup Integer file
Refer to Troubleshooting the
Invalid Backup State section,
later in this chapter.
Off
This processor is not the primary (i.e., system is
in the No Control or Secondary backup state).
Normal operation
No action required
SEC
Yellow
This processor is the qualified secondary (i.e.,
system is in the Secondary backup state).
Normal operation
No action required
Red
The backup system is not yet completely
configured (i.e., system is in the Invalid backup
state).
Improper backup
configuration
parameters
Improper ControlNet
Backup Integer file
Refer to Troubleshooting the
Invalid Backup State section,
later in this chapter.
Off
This processor is not the secondary (i.e., system
is in the No Control or Primary backup state).
Normal operation
No action required
QUAL
Green
The system has both a primary and a secondary
processor, which are communicating properly
with each other; the secondary processor is
qualified.
Normal operation
No action required
Yellow
The system has both a primary and a secondary
processor, which are communicating properly
with each other, but the secondary is not yet
qualified.
Normal operation
No action required
Alternating yellow
and green
Qualification active
Normal operation
No action required
Off
The primary and secondary processors are not
communicating properly with each other.
Standalone processor
One or both processors
are in the Invalid
backup state
Improper backup
configuration
parameters
Verify that the connection
parameters (words 0 - 2) of the
ControlNet Backup Integer file
are the same for both processors.