SLC™ 500 4-Channel Analog I/O Modules 5
Publication 1746-IN008C-EN-P - May 2004
Analog Modules Operation
The module converts analog input signals to 16-bit binary values for storage in the
SLC processor’s input image table. The decimal range, number of significant bits,
and converter resolution depend on the input range that you use for the channel.
Analog Input A/D Characteristics
Analog Output D/A Characteristics
The analog modules have the same output characteristics.
NI4, NIO4I, & NIO4V Input
Range
Decimal Range (input
image table)
Number of
Significant Bits
Nominal Resolution
±10V dc -1 LSB
-32,768 to +32,767
16
305.176 µV/LSB
0 to 10V dc -1 LSB
0 to 32,767
15
0 to 5V dc
0 to 16,384
14
1 to 5V dc
3,277 to 16,384
13.67
±20 mA
±16,384
15
1.22070 µA/LSB
0 to 20 mA
0 to 16,384
14
4 to 20 mA
3,277 to 16,384
13.67
FIO4I and FIO4V Input
Range
Decimal Range (input
image table)
Number of
Significant Bits
Nominal Resolution
0 to 10V dc -1 LSB
0 to 4095
12
2.4414 mV/LSB
0 to 5V dc
0 to 2047
11
1 to 5V dc
409 to 2047
10.67
0 to 20 mA
0 to 2047
11
9.7656 µA/LSB
4 to 20 mA
409 to 2047
10.67
Module
Output Range
Decimal Range (output
image table)
Significant Bits Resolution
FIO4I
NIO4I
NO4I
0 to 21 mA - 1 LSB
0 to 32,764
13 bits
2.56348 µA/LSB
0 to 20 mA
0 to 31,208
12.92 bits
4 to 20 mA
6,242 to 31,2089
12.6 bits
FIO4V
NIO4V
NO4V
±10V dc - 1 LSB
-32,768 to +32,764
14 bits
1.22070 mV/LSB
0 to 10V dc -1 LSB
0 to 32,764
13 bits
0 to 5V dc
0 to 16,384
12 bits
1 to 5V dc
3,277 to 16,384
11.67 bits
@JO$&/QQE