A - specifications, Specifications – Rockwell Automation 1791-IOBB USER MANUAL User Manual
Page 30
Appendix
A
AĆ1
Specifications
General Specifications
External power
200mA @ 24V dc; initial surge 5.5A for 10
µ
sec.
The supply must be able to source an additional 100mA
plus an inrush current of 400mA when a peripheral is
connected.
Environmental Conditions
Operating Temperature
Storage Temperature
Relative Humidity
32 to 131
o
F (0 to 55
o
C)
-40 to 185
o
F (-40 to 85
o
C)
5 to 95% noncondensing
Conductors Wire Size
14 gauge stranded (maximum)
3/64 inch insulation (maximum)
Power Dissipation
IOBA/B: 13.94 Watts (maximum); 9.62 Watts (typical)
IOBB/B: 13.05 Watts (maximum); 8.92 Watts (typical)
Thermal Dissipation
IOBA/B: 47.7 BTU/hr (maximum); 32.9 BTU/hr (typical)
IOBB/B: 44.6 BTU/hr (maximum); 30.5 BTU/hr (typical)
Remote I/O Isolation
850V dc (transformer) for 1 second
DH-485 Isolation
850V dc (optocoupler) for 1 second
Interconnect cable length
RIO: PLC 57.6K
10,000 cable-feet
115.2K
5,000 cable-feet
230.4K
2,500 cable-feet
SLC 230.4K
2,500 cable-feet
DH-485
4000 ft (1219 meters)
Cable requirements
RIO/DIO - Belden 9463
DH-485 - Belden 9842
1791-IOBA/B Input Specifications
Number of Inputs
8
Input type
Sinking
Input voltage range
20.5 to 27.6V dc
On-state input current
6.5mA (minimum) @ 20.5V dc
On-state input voltage
20.5V dc (minimum)
Off-state voltage
6.0V dc (maximum)
Off-state current
1.5mA dc (maximum)
Turn On time
1.5msec (maximum)
Turn Off time
1.0msec (maximum)