Installing Block I/O

Chapter 2

2Ć2

Maximum

Network Distance

Baud Rate

Used

Maximum Capacity

and

When using

/

57.6K

10,000 cable-feet

PLC-5 family (continued)

PLC-5/30

28 blocks/channel, 28 blocks per

processor with 82 ohm terminator

115.2K

5,000 cable-feet

processor with 82 ohm terminator

230.4K

2,500 cable-feet

16 blocks/channel, 32 blocks per

57.6K

10,000 cable-feet

16 blocks/channel, 32 blocks per

processor with 150 ohm terminator

115.2K

5,000 cable-feet

PLC-5/40L, PLC-5/60L

/

57.6K

10,000 cable-feet

32 blocks/channel, 60 blocks per

processor with 82 ohm terminator

115.2K

5,000 cable-feet

processor with 82 ohm terminator

230.4K

2,500 cable-feet

16 blocks/channel, 60 blocks per

57.6K

10,000 cable-feet

16 blocks/channel, 60 blocks per

processor with 150 ohm terminator

115.2K

5,000 cable-feet

PLC-5/40, PLC-5/60

/

57.6K

10,000 cable-feet

32 blocks/channel, 60 blocks per

processor with 82 ohm terminator

115.2K

5,000 cable-feet

processor with 82 ohm terminator

230.4K

2,500 cable-feet

16 blocks/channel, 32

blocks/scanner 64 blocks/(2

57.6K

10,000 cable-feet

PLC 5250

i

blocks/scanner, 64 blocks/(2

scanners) with 150 ohm terminator

115.2K

5,000 cable-feet

PLC-5250 - requires

a 5150-RS remote scanner

32 blocks/channel 32

57.6K

10,000 cable-feet

a 5 50 S e o e sca e

32 blocks/channel, 32

blocks/scanner, 64 blocks/(2

scanners) with 82 ohm terminator

115.2K

5,000 cable-feet

scanners) with 82 ohm terminator

230.4K

2,500 cable-feet

SLC-5/01 Controller

1747-DSN Scanner module*

7 blocks

230.4K

2,500 cable-feet

SLC-5/02 Controller

1747-DSN Scanner module*

30 blocks

230.4K

2,500 cable-feet

S

/O

57.6K

10,000 cable-feet

SLC-5/02 Controller

1747-SN Remote I/O

Scanner Module*

16 blocks

115.2K

5,000 cable-feet

Scanner Module

230.4K

2,500 cable-feet

* The DH-485 network, which operates independent of the remote I/O/distributed I/O network, supports up to 30 DH-485 nodes (blocks or

1747-AIC isolated couplers). The maximum DH-485 network distance is 4,000 cable-feet.