beautypg.com

Figure 6 - discrete device wiring – Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual

Page 16

background image

16 Compact I/O High-speed Counter Module

Publication 1769-IN030B-EN-P - October 2010

Figure 6 - Discrete Device Wiring

(1)

External resistors are required if they are not internal to the sensor. The pull-up resistor (R) value depends on the power
supply value. The table shows the maximum resistor values for typical supply voltages. To calculate the maximum resistor
value, use the following formula:

where:

R = maximum pull-up resistor value

V DC = power supply voltage

V min = 2.6V DC

I min = 6.8 mA

The minimum resistor (R) value depends on the current sinking capability of the sensor.
Refer to your sensor’s documentation.

Power Supply Voltage (V DC)

Pull-up Resistor Value (R), Max

(1)

(1)

Resistance values may change, depending upon your application.

5V DC

352

Ω

12V DC

1382

Ω

24V DC

3147

Ω

VS

A1(+)

A1(–)

B1(+)

B1(–)

Z1(+)

Z1(–)

+VDC

COM

VS

OUT

COM

OUT

COM

VS

OUT

COM

R

(1)

Power
Supply

Module Inputs

Solid-state
Switch

Proximity Sensor

Photo-electric Sensor with
Open Collector Sinking
Output

R

VDC

Vmin

(

)

Imin

---------------------------------------------

=