LED Status Indicators
Interpreting the Status
Indicators
The faceplate of the 1756-ENET/B module is provided with LED
indicators that display the module status and transmit/receive status.
The following table describes module health indicator displays,
module status, and recommended action:
The following table describes the displays of the transmit (TX) and
receive (RX) indicators:
Detailed network diagnostics are provided by the module’s Web
pages, which can be accessed through Netscape or Microsoft Internet
Explorer. See Appendix B.
If the OK indicator is:
then module status is:
take this action:
Off
Not operating.
Apply chassis power.
Verify module is completely
inserted into chassis and
backplane.
Red, then flashing red
or flashing green
Performing powerup
diagnostics.
None, normal operation.
Green
Operating.
None.
Red flashing
Not configured.
Configure the module.
Red
Unrecoverable fault.
Repair or replace module.
If this indicator: is:
the module is:
TXD
Green
Transmitting data
Off
Not active
RXD
Green
Receiving data
Off
Not active
31153-M
AUI
10 BASET
1756-ENET
RXD TXD OK
ETHERNET
TXD
Indicator
OK Indicator
RXD
Indicator
Front View